Every type of smoke alarm, explained

The differences that matter are not cosmetic. Power source decides whether the alarm survives a power cut; the interconnection decides whether everyone in the building hears it; the sensing technology decides whether it cries wolf.

By power source

Battery-only (standalone)

A 9 V alkaline, a 9 V lithium or a sealed 10-year lithium cell. No wiring, installable in minutes, suited to older buildings and rented flats. The failure mode is human: the battery is removed to silence a nuisance alarm and never replaced.

Typical life: 1 year (alkaline), 5–10 years (lithium), 10 years (sealed)

Mains-powered with battery backup

Runs from the building supply with a rechargeable or replaceable backup cell. No routine battery changes, and the units can be wired together so that one alarm sounds them all. Requires a permanent, fused, regularly used lighting circuit — never a switched socket.

Typical backup: 7 days standby or 4 minutes in alarm
The sealed 10-year battery is the modern default

In Europe and North America the tamper-proof sealed unit is now the usual specification for rented housing, precisely because it cannot be raided for a battery. Where legislation requires a 10-year sealed unit, a removable-battery alarm does not comply even if its battery happens to be lithium.

By interconnection

ArrangementHow it worksStrengthsWatch out for
StandaloneOne device, one sounderCheapest; no wiring; ideal for a single roomNobody hears an alarm that fires in a closed room at the far end of the house
Hardwired interlinkA communication conductor between mains units, usually three-core plus earthDeterministic, no radio, no battery dependency for the link, no pairingRequires cable and a competent electrician; hard to retrofit into a finished home
Wireless interlinkSub-GHz or 2.4 GHz radio mesh between unitsRetrofits into any building; mixes mains and battery units; pairs in minutesRadio range through reinforced concrete or metal; pairing and house-coding must be done properly
System with panelDetectors on a loop reporting to a control panelZonal identification, monitored circuits, integration with sounders, beacons and call pointsDesign and commissioning by a qualified contractor; not a homeowner product
Diagram comparing hardwired interlink and wireless mesh interlink topologies across a two-storey house
Interconnection topologies. Left: a hardwired three-conductor interlink between mains units. Right: a wireless mesh in which the first alarm transmits to its neighbours, which relay the message onward — so every device sounds even where the radio path to the furthest unit is indirect.

By capability

Grades and categories — the language of fire codes

British and many European specifications describe what you install with a letter grade and where you install it with a category. Once you can read the two together, a specification such as “Grade D2, LD2” stops being jargon and becomes an instruction.

Grading of fire detection for dwellings (BS 5839-6 style)
GradeWhat it means
Grade ASeparate detectors on a fire panel, with sounders — used in large or complex residential buildings
Grade BSeparate detectors and sounders on a control unit, with central power
Grade CSeparate detectors and sounders on a control unit, using local mains power
Grade DOne or more mains-powered smoke alarms with a standby supply — the common domestic specification
Grade EMains-powered smoke alarms without a standby supply (no protection in a power cut)
Grade FBattery-only smoke alarms — the minimum where nothing else is practicable
Categories — how much of the dwelling is protected
CategoryCoverage
LD1Highest: alarms in all circulation areas plus every room where a fire could start, apart from rooms with a low fire risk
LD2Aimed at escape routes: circulation areas plus the rooms used as sleeping accommodation and the principal living space
LD3Escape routes only: circulation areas between the sleeping area and the final exit
What does the law actually require?

Grades and categories are design language, not law in themselves — the law cites them. National and regional requirements differ widely and change regularly, so check the standards and regulations page and confirm locally before specifying.

Practical selection in four questions

  1. Is this a dwelling or a managed building?A dwelling almost always takes Grade D or F self-contained alarms. Any building with a fire strategy, sleeping strangers or an evacuation plan usually needs a panel-based system.
  2. What is the room?Smoke sensing for circulation and sleeping spaces; heat sensing for kitchens, garages and dusty rooms; CO sensing where combustion appliances or vehicle exhaust can leak in.
  3. Do all the devices need to sound together?In almost every occupied building, yes. Wireless interlinking lets you achieve that without opening ceilings.
  4. Who will maintain it?A landlord, a maintenance contractor and a family in a private house need different accessibility. Choose units whose test, silence and replacement you can actually perform.